NBC 2020 Firestopping Requirements: What Changed for Joints and Penetrations
September 14, 2026

Fire separations are designed to restrict the spread of fire and smoke, but joints, service penetrations and recessed boxes can compromise that protection. The 2020 National Building Code of Canada introduced clearer firestopping requirements for these conditions, especially for joints and perimeter fire containment systems.
NBC 2020 requires firestopping to be evaluated as a complete system, not simply as a material applied to an opening. The code adds specific testing and rating requirements for joints, clarifies requirements for penetrations and outlet boxes, and strengthens expectations for matching listed systems to actual construction conditions.
- Firestopping is a tested system made up of materials, components and means of support.
- Most joints in or between fire-resistance-rated assemblies require an FT-rated system tested to CAN/ULC-S115.
- Perimeter joints at curtain walls require a system tested to ASTM E2307 and need an F rating.
- Through-penetration firestops generally require an F rating equal to the required fire-resistance rating, with FT ratings required in a few specific applications.
- Tested systems are very specific and must match the field conditions, including the assembly, penetrating item, opening size, annular space, materials, movement and installation details.
Joint Firestop Systems Now Have Specific Requirements
For a fire-resistance-rated separation that abuts another fire separation, floor, ceiling or roof, NBC 2020 generally requires continuity to be maintained with a firestop having an FT rating not less than the rating of the adjoining fire separation. The system is evaluated using CAN/ULC-S115.
The F rating measures how long the system prevents flame passage. The T rating measures how long the unexposed side remains below the test standard’s temperature-rise limit. An FT-rated system must satisfy both criteria.
Joint movement must also be addressed. Floors deflect under load, materials expand and contract, wind moves building assemblies, and seismic activity can impose additional movement. The selected joint system must accommodate the movement expected during the building’s service life. A static system should not be accepted where the joint is expected to move.
This requirement does not mean every joint between gypsum panels needs a separate firestop system. Butted joints, corners and intersections constructed as required by the listed fire-resistance-rated assembly may be finished according to that assembly. Once an unintended gap exists, the condition must be evaluated rather than treated as a routine board joint.
Perimeter Fire Containment Is a Whole-System Condition
The joint between a floor slab and an exterior curtain wall presents a different fire exposure. NBC 2020 requires applicable horizontal perimeter joints to be protected by a system tested to ASTM E2307, with an F rating not less than the required fire-resistance rating of the floor assembly.
ASTM E2307 evaluates more than the material placed in the safing gap. It considers how the curtain wall assembly behaves when exposed to fire from inside the building and from flames extending through a window opening. The spandrel construction, spandrel height and position, insulation, reinforcement, safing material, compression and joint coating can all affect performance.
For that reason, a perimeter fire containment design or engineering judgment should closely match the curtain wall installed on the project. A detail addressing only the slab-edge gap, without accounting for the wall construction and its expected fire behaviour, does not provide the same level of evidence as a representative tested system.
Penetration Firestops: Know When F or FT Applies
Penetrations through a fire separation, or through a membrane that protects a rated assembly, must be sealed with a firestop tested to CAN/ULC-S115. Under NBC 2020, the required F rating is generally not less than the required fire-resistance rating of the fire separation.
An FT rating is required for certain higher-risk conditions identified by the code, including penetrations in firewalls, specified horizontal separations above garages and horizontal service space separations. Project teams should confirm the exact code condition before specifying a rating. Requiring FT protection where the code does not call for it will add unnecessary insulation, complexity and cost.
Membrane penetrations deserve the same careful review. In some floor-ceiling assemblies, the gypsum board or other ceiling membrane protects structural members with limited inherent fire resistance. An unprotected opening in that membrane can prematurely expose the structural elements to the intense heat of a fire and cause assembly failure during a fire incident.
Cast-in-Place Does Not Automatically Mean Compliant
NBC 2020 clarifies that the cast-in-place provision applies only to specified penetrating items that will not melt or burn, such as steel, ferrous metal, copper, concrete or masonry. It also requires the condition to be free of gaps between the penetrating item and the assembly.
A steel sleeve cast into concrete does not protect the services routed through it in the least. If cables, pipes or other items pass through the sleeve, the remaining opening must still be protected with an appropriate firestop system. Combustible sleeves and penetrating items do not fall under the code’s cast-on-place allowance since the items will melt and/or burn, leaving behind a gap for fire and smoke spread.
Cast-in firestop devices can simplify this condition by incorporating the firestop components into a tested device before the concrete is poured. The device must still be selected and installed for the intended assembly and service penetration.
Outlet Boxes and Part 9 Buildings Still Require Attention
NBC 2020 requires combustible outlet boxes and other recessed service boxes in rated assemblies to be protected by an FT-rated system. Certain steel outlet boxes may qualify for an exemption, but only when all applicable limits are met, including box size, aggregate area, annular space and separation from boxes on the opposite side of the wall. The membrane penetration firestopping requirements are identical in Part 3 and and 9 of the NBC.
Part 9 buildings are not broadly exempt from firestopping. Joint and perimeter joint requirements generally align with those in Part 3. Some through-penetration conditions in Part 9 may permit alternate methods, but the applicable provision must be reviewed for the specific assembly and building condition. Where a tested firestop system is available, it provides clearly defined materials, dimensions and installation criteria for verification.
What Design and Inspection Teams Should Verify
Effective review begins with the listed system number. From there, confirm that the fire-resistance rating, test standard and required F or FT rating are correct. Then compare the listing with the field condition, including the wall or floor construction, penetrating item, sleeve, opening size, annular space, packing material, sealant depth, movement capability and any required insulation or reinforcement.
If the installed condition falls outside the tested listing, it should not be accepted based only on product familiarity or visual appearance. The project team should obtain an appropriate tested system or a properly documented technical evaluation (engineering judgment) from the firestop manufacturer, subject to acceptance by the authority having jurisdiction.
Strengthen Firestop Compliance on Canadian Projects
Clear specifications, listed systems and accurate field verification help preserve the performance of fire separations and reduce preventable corrections during construction.
Explore IFC Canadian firestop resources
Canadian code officials may also request an IFC live, in-person NBC firestopping seminar by contacting info@firestop.org.
Code adoption and enforcement vary by province, territory and local jurisdiction. The 2025 National Model Codes are now available, but the model codes take legal effect only when adopted by the applicable authority. Review the provincial and territorial adoption information and confirm the governing code and amendments with the local authority having jurisdiction.